Skip to content
VoltAire HTC042B HTC Counter Flow heat exchanger (representative product photo — actual unit photography forthcoming)

HTC Counter Flow

HTC042B

42 W/°F htc counter flow air-to-air heat exchanger. 48VDC input.

Starting Price

$2,755

Integrator pricing available • Volume discounts on 5+ units

Built to Order 4-6 weeks lead time typical
NEMA 4 / 4X UL 1995 Listed GR-487 BABA Eligible Made in USA −40°F to 158°F

Technical Specifications

HTC042B at a glance

Capacity
42 W/°F (watts removed per °F of cabinet-to-ambient ΔT)
Series
HTC Counter Flow
Flow Configuration
Counter Flow
Voltage
48VDC
Fan Power (typical)
100 W
Sound Level
66 dBa @ 6 ft
Outer Dimensions (W × H × D)
16.1 × 24.0 × 11.3″
Cutout (W × H)
16.1 × 24.0″
Weight
45 lbs
Operating Range
−40°F to 158°F (−40°C to 70°C)
Salt Fog Tested
720 hours per ASTM B117 (GR-487 Issue 5)

Specifications subject to change. Always verify against the current spec sheet before final design submittal.

Model Number Decoded

What does HTC042B mean?

H T C 0 4 2 B
  • H = Heat exchanger
  • T = Telecom series (telecom)
  • C = Counter Flow configuration
  • 042 = 42 W/°F capacity
  • B = 48VDC input

Where HTC042B Fits

Best applications for this model

HTC042B is sized for cabinets where the internal heat load is in the range that 42 W/°F can move at your available temperature differential. As a quick rule of thumb, multiply 42 by your ambient-to-target ΔT to get the maximum heat load (in watts) this unit can handle. For example, at a 20°F ΔT this model removes 840W; at a 30°F ΔT, 1260W.

Watch: Cross Flow vs. Counter Flow

Common use cases

5G macro-site cabinets, BEAD broadband fiber huts, edge-compute enclosures, mid-size process control panels.

Voltage fit

Direct connection to −48V telecom plant . No inverter required. Battery-resilient cooling.

Ready to spec HTC042B?

Quotes returned same day. Integrator pricing on request. Built and shipped from Orlando, FL with US-stocked replacement parts.