HTC Counter Flow
HTC015B
15 W/°F htc counter flow air-to-air heat exchanger. 48VDC input.
Pricing
Call us for a quote
Quotes typically returned same-day. Integrator and volume discounts available.
Technical Specifications
HTC015B at a glance
- Capacity
- 15 W/°F (watts removed per °F of cabinet-to-ambient ΔT)
- Series
- HTC Counter Flow
- Flow Configuration
- Counter Flow
- Voltage
- 48VDC
- Fan Power (typical)
- 18 W
- Sound Level
- 51 dBa @ 6 ft
- Outer Dimensions (W × H × D)
- 12.3 × 20.0 × 7.6″
- Cutout (W × H)
- 9.0 × 20.0″
- Weight
- 22 lbs
- Operating Range
- −40°F to 158°F (−40°C to 70°C)
- Salt Fog Tested
- 720 hours per ASTM B117 (GR-487 Issue 5)
Specifications subject to change. Always verify against the current spec sheet before final design submittal.
Model Number Decoded
What does HTC015B mean?
- H = Heat exchanger
- T = Telecom series (telecom)
- C = Counter Flow configuration
- 015 = 15 W/°F capacity
- B = 48VDC input
Where HTC015B Fits
Best applications for this model
HTC015B is sized for cabinets where the internal heat load is in the range that 15 W/°F can move at your available temperature differential. As a quick rule of thumb, multiply 15 by your ambient-to-target ΔT to get the maximum heat load (in watts) this unit can handle. For example, at a 20°F ΔT this model removes 300W; at a 30°F ΔT, 450W.
Watch: Cross Flow vs. Counter Flow
Common use cases
Outdoor telecom RTUs, fiber distribution cabinets, small-cell shelters, pipeline SCADA panels.
Voltage fit
Direct connection to −48V telecom plant . No inverter required. Battery-resilient cooling.
Other Models in the HTC Series
Need a different size or voltage?
Ready to spec HTC015B?
Quotes returned same day. Integrator pricing on request. Built and shipped from Orlando, FL with US-stocked replacement parts.