HIX Cross Flow
HIX055N
55 W/°F hix cross flow air-to-air heat exchanger. 230VAC input.
Pricing
Call us for a quote
Quotes typically returned same-day. Integrator and volume discounts available.
230VAC is priced per order — send a quick request and we'll get you a number, usually same day.
Technical Specifications
HIX055N at a glance
- Capacity
- 55 W/°F (watts removed per °F of cabinet-to-ambient ΔT)
- Series
- HIX Cross Flow
- Flow Configuration
- Cross Flow
- Voltage
- 230VAC
- Fan Power (typical)
- 95 W
- Sound Level
- 68 dBa @ 6 ft
- Outer Dimensions (W × H × D)
- 17.8 × 35.5 × 8.5″
- Cutout (W × H)
- 16.5 × 34.0″
- Weight
- 55.5 lbs
- Operating Range
- −40°F to 158°F (−40°C to 70°C)
- Salt Fog Tested
- 720 hours per ASTM B117 (GR-487 Issue 5)
Specifications subject to change. Always verify against the current spec sheet before final design submittal.
Model Number Decoded
What does HIX055N mean?
- H = Heat exchanger
- I = Industrial series (industrial / utility)
- X = Cross Flow configuration
- 055 = 55 W/°F capacity
- N = 230VAC input
Where HIX055N Fits
Best applications for this model
HIX055N is sized for cabinets where the internal heat load is in the range that 55 W/°F can move at your available temperature differential. As a quick rule of thumb, multiply 55 by your ambient-to-target ΔT to get the maximum heat load (in watts) this unit can handle. For example, at a 20°F ΔT this model removes 1100W; at a 30°F ΔT, 1650W.
Watch: Cross Flow vs. Counter Flow
Common use cases
Equipment shelters, telecom huts, large outdoor industrial enclosures, high-density edge data center cabinets.
Voltage fit
230V single-phase utility power. Common in larger industrial enclosures and international installations.
Other Models in the HIX Series
Need a different size or voltage?
Ready to spec HIX055N?
Quotes returned same day. Integrator pricing on request. Built and shipped from Orlando, FL with US-stocked replacement parts.